Industrial fuse replacement guide showing KRP-C-800SP, LP-CC-10 and AJT60, with checks for class, AC/DC voltage, time delay, interrupting rating and physical fit.

When equipment goes down, everybody wants the replacement yesterday. We understand that. But getting a part there fast only helps if it is the right part. With industrial fuses, matching the amperage is just the starting point.

The fuse class, voltage rating, time-delay characteristics, interrupting rating, and physical connections all matter. A fuse that looks close—or carries the same amp rating—does not automatically provide the protection your equipment requires.

At Essential Electric, we want to help you get the details right before a replacement is on its way. Here is what to check, using four real parts: KRP-C-800SP, LP-CC-10, FLSR-020ID, and AJT60.

What must match when replacing an industrial fuse?
Verify the complete catalog number, specified amp rating, fuse class, applicable AC or DC voltage rating, operating characteristics, interrupting rating, and physical fit against the equipment requirements. An alternate needs a documented application review—not just a matching amp number.

Four fuse examples—and the details that separate them

These parts illustrate different fuse families. They are not a cross-reference or a list of interchangeable replacements.

Part Manufacturer Amps AC rating Class What to notice
KRP-C-800SP Eaton Bussmann 800 A 600 VAC L Time-delay; bolted blade connections
LP-CC-10 Eaton Bussmann 10 A 600 VAC CC Time-delay; rejection-style ferrule fuse
FLSR-020ID Littelfuse 20 A 600 VAC RK5 Dual-element, time-delay, indicating; manufacturer catalog number FLSR020ID
AJT60 Mersen 60 A 600 VAC J Time-delay; ferrule connections

Specifications checked against Eaton KRP-C-800SP, Eaton LP-CC-10, Littelfuse FLSR_ID documentation, and Mersen AJT60. The table shows AC ratings; verify the separate DC rating when applicable. Product photos are for identification, not scale.

1. Start with the entire part number

Send the manufacturer and every character you can read on the label. Include prefixes, suffixes, fractions, and any indication markings. A partial number makes it easier to select the wrong family or overlook a feature.

For example, our FLSR-020ID listing uses a hyphen, while Littelfuse lists the manufacturer catalog number as FLSR020ID. Its ordering table identifies that part as 20 amps. Photographing the label is more useful than trying to describe it from memory.

If the old part is unreadable, send what you have along with the equipment information. We can help narrow down the identification; the equipment requirements still need to be verified.

2. Match the required fuse class and mounting arrangement

Class L, Class CC, Class RK5, and Class J are different fuse classifications. Do not treat them as different brand names for the same thing.

The KRP-C-800SP uses bolted blade connections. The LP-CC-10 has a much smaller rejection-style ferrule construction. The AJT60 is a Class J ferrule fuse. Those physical details are part of the selection—not an inconvenience to work around.

A fuse fitting into a holder is not enough to establish that it is suitable. Check the holder or disconnect markings and the equipment documentation. Do not modify clips, bypass rejection features, or improvise an adapter to make an unverified substitute fit.

3. Check voltage and interrupting ratings separately

The amp rating and voltage rating answer different questions. A replacement must have the specified current rating and a voltage rating suitable for the circuit. AC and DC ratings are separate; do not carry an AC rating over to a DC application.

The interrupting rating addresses the fault current a fuse can interrupt under its specified conditions. It is not its normal operating current, and it is not interchangeable with the equipment’s overall short-circuit current rating.

If you are considering a different catalog number, have a qualified person verify the available fault current, required interrupting capability, and the equipment’s ratings and documentation. “It is also 600 volts” does not complete that review.

4. Time-delay does not mean every time-delay fuse behaves alike

All four examples above are time-delay fuses, but that label alone does not make them equivalent. The relevant time-current curves and the protected load still matter.

Motor or transformer starting current is one reason operating characteristics matter. A replacement should meet the equipment’s specified protection requirements, including any coordination requirements. Do not substitute a fast-acting fuse for a time-delay type—or choose a larger amp rating to stop repeated opening—without an appropriate technical review.

A fuse that opens again is a reason to investigate the circuit and load, not simply order a bigger fuse.

5. Treat indication as a feature, not the entire diagnosis

Littelfuse’s FLSR_ID family includes a visual blown-fuse indicator. That can help with identification, but it does not explain why the fuse opened or prove equipment is safe to work on. Preserve required features when evaluating a replacement and follow the site’s electrical safety and testing procedures.

What to send us when you need a replacement fast

A few clear details can save a lot of back-and-forth. Send:

  • A readable photo of the full fuse label and catalog number.
  • Photos showing both ends and the connection style, obtained safely.
  • The holder, switch, or equipment manufacturer and model, plus its fuse requirements.
  • The quantity needed, delivery ZIP code, and when the part must arrive.
  • Whether you need the exact part or want us to help research an alternate for technical approval.

Have qualified personnel obtain any photos that require access to electrical equipment, following applicable isolation and safety procedures. There is no need to expose yourself to energized equipment to get us a better picture.

For urgent orders, tell us the deadline at the start. We can check current inventory and available shipping options for the specific part and destination. Confirm availability and timing with our team before relying on an arrival date.

Keep the next replacement from becoming another emergency

Once your team has verified a replacement, record the full catalog number, equipment location, quantity, and supporting documentation. Then decide which items belong in your spare-parts inventory based on downtime risk and replenishment needs.

Our critical electrical spare-parts checklist walks through that planning. The goal is to put your maintenance team in a better position before the next interruption.

Industrial fuse replacement questions

Can I replace a fuse with another brand if the amperage matches?

Matching amperage alone is insufficient. A qualified review must confirm the fuse class, AC/DC voltage rating, operating characteristics, interrupting rating, physical fit, and equipment requirements. Use a documented manufacturer cross-reference where available and verify it for the application.

Are Class CC and midget fuses interchangeable?

Do not assume so because their bodies look similar. The LP-CC-10 is a Class CC rejection-style fuse. Confirm the required fuse class and holder compatibility rather than selecting by appearance.

What if the fuse number is worn off?

Send readable portions of the label, safe photos, and equipment and holder information. Our team can help research the part. Do not infer the required fuse solely from another fuse nearby.

Need help identifying your fuse?

Call (866) 377-3532 with the part number, quantity, delivery ZIP code, and deadline. Our team will help you check the details and available options.

Browse industrial fuses →

This is a purchasing and identification guide, not an installation procedure or approval of a substitute. Fuse selection, troubleshooting, and replacement should be performed or approved by qualified personnel using the equipment and manufacturer documentation.