2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
SK3A1000PB3S
Hammond Power Solutions SK3A1000PB3S is a three-phase general duty transformer designed for industrial power distribution applications. This unit features a 600V delta primary configuration stepping down to 208Y/120V secondary with a 1000 kVA capacity and operates at 60Hz with a standard impedance range of 4% to 7.5%. Constructed with aluminum windings and housed in a Type 3R/IP24 rated enclosure with ANSI 61 grey finish, the transformer measures 82"H x 60"W x 47"D and is designed for 150°C temperature rise with 220°C insulation class. The transformer complies with DOE 2016, NRCAN 2019, and NMX 2021 efficiency regulations and meets IBC 2018 seismic requirements (Sds=2.0, z/h=0, lp=1.5) while operating at 67 dBA sound levels. Typical applications include industrial facilities, manufacturing plants, and commercial buildings requiring reliable three-phase power conversion with electrostatic shielding and mounting pad terminations. Key Features & Specifications
- Type: Three-Phase General Duty Transformer
- Primary Voltage: 600V Delta
- Secondary Voltage: 208Y/120V Wye-N
- kVA Rating: 1000 kVA (1358.31 EKVA)
- Frequency: 60Hz
- Impedance: 4% - 7.5%
- Enclosure: Type 3R / IP24, ANSI 61 Grey
- Dimensions: 82"H x 60"W x 47"D (2083mm x 1524mm x 1194mm)
- Temperature Rise: 150°C
- Insulation Class: 220°C
- Material: Aluminum Windings
- Sound Level: 67 dBA (NEMA ST-20)
- Efficiency Compliance: DOE 2016, NRCAN 2019, NMX 2021
- Seismic Standard: IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Vector Configuration: Dyn1 (-30°)
Specifications
- Part Number: SK3A1000PB3S
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 600D
- Primary Connection : Delta
- Secondary Voltage : 208Y/120
- Secondary Connection : Wye-N
- Material : Aluminum
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 1358.31
- Efficiency Regulation : DOE 2016 (US), NRCAN 2019 (Canada), NMX 2021 (Mexico)
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 67 dBA (NEMA ST-20)
- Impedance (Std) : 4% - 7.5%
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure Dimensions : 82in/2083mm(H), 60in/1524mm(W), 47in/1194mm(D)
- Electrostatic Shield : Single
- Nameplate : Standard
- Standard kVA : 1000
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
- Primary FCAN (Std) : 2x2.5%
- Primary Termination (Std) : Mounting Pads
Product Data
- UPC : 803423130428
- Weight : 5.19
- Certification : CSA, UL