- Manufacturer:Hammond Power Solutions
Description
SG3C0112KD
Hammond Power Solutions SG3C0112KD is a three-phase general duty transformer designed for industrial power distribution applications. The unit features a 480V delta primary configuration with multiple 2.5% FCAN/FCBN taps and delivers 240/120V secondary output at 112.5 kVA capacity with aluminum windings rated for 150°C temperature rise and 220°C insulation class. Constructed with a Type 3R/IP24 rated enclosure finished in ANSI 61 grey, the transformer measures 36 inches in height, 28.25 inches in width, and 27 inches in depth while operating at a quiet 50 dBA sound level. This transformer complies with DOE 2016, NRCAN 2019, and NMX 2021 efficiency regulations and meets IBC 2018 seismic requirements (Sds=2.0, z/h=1, lp=1.5). Typical applications include industrial facilities, manufacturing plants, and commercial buildings requiring reliable three-phase power conversion. Key Features & Specifications
- Type: Three-Phase General Duty Transformer
- Primary Voltage: 480V Delta
- Secondary Voltage: 240/120V
- kVA Rating: 112.5
- Frequency: 60Hz
- Material: Aluminum Windings
- Temperature Rise: 150°C
- Insulation Class: 220°C
- Impedance: 2.5% - 6.5%
- Enclosure: Type 3R / IP24
- Dimensions: 36"H × 28.25"W × 27"D
- Sound Level: 50 dBA
- Efficiency Compliance: DOE 2016, NRCAN 2019, NMX 2021
- Seismic Standard: IBC 2018
Specifications
- Part Number: SG3C0112KD
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 480D
- Primary Connection : Delta
- Primary FCAN (NPL) : 2x2.5%
- Primary FCBN (NPL) : 4x2.5%
- Secondary Voltage : 240/120
- Material : Aluminum
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 112.5
- Efficiency Regulation : DOE 2016 (US), NRCAN 2019 (Canada), NMX 2021 (Mexico)
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=1, lp=1.5)
- Sound Level : 50 dBA (NEMA ST-20)
- Impedance (Std) : 2.5% - 6.5%
- Secondary Termination (NPL) : Mechanical Lugs
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : DH3-N3R
- Enclosure Dimensions : 36in/915mm(H), 28.25in/718mm(W), 27in/686mm(D)
- Nameplate : Standard
- Standard kVA : 112.5
- Vector Configuration : Dd0 (0°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=1
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423124281
- Weight : 690
- Certification : CSA, UL