- Manufacturer:Hammond Power Solutions
Description
SG3A0112KB0C
SG3A0112KB0C is a 112.5 kVA, 3 phase dry type transformer from Hammond Power Solutions designed for low voltage distribution applications.This transformer features a 480 Volt Delta primary and 208Y/120 Volt secondary voltage configuration. It is copper wound and built to meet DOE 2016 and NRCan 2019 energy efficiency standards. The unit operates at 60 Hz frequency and is rated for a 150°C temperature rise with a heavy duty ventilated Type 3R enclosure. It is suitable for general purpose distribution use and complies with industry standards for energy efficient transformers.
- Power Rating: 112.5 kVA
- Phase: 3 Phase
- Primary Voltage: 480V Delta
- Secondary Voltage: 208Y/120V
- Winding Material: Copper
- Frequency: 60 Hz
- Temperature Rise: 150°C
- Enclosure Type: Type 3R ventilated
- Energy Efficiency: DOE 2016 and NRCan 2019 compliant
- Mounting Type: Floor (DH3 case style)
Specifications
- Part Number: SG3A0112KB0C
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 480D
- Primary Connection : Delta
- Primary FCAN (NPL) : 2x2.5%
- Primary FCBN (NPL) : 4x2.5%
- Secondary Voltage : 208Y/120
- Secondary Connection : Wye-N
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 112.5
- Efficiency Regulation : DOE 2016 (US), NRCAN 2019 (Canada), NMX 2021 (Mexico)
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=1, lp=1.5)
- Sound Level : 50 dBA (NEMA ST-20)
- Impedance (Std) : 2.5% - 6.5%
- Secondary Termination (NPL) : Mounting Pads
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : DH3-N3R
- Enclosure Dimensions : 36in/915mm(H), 28.25in/718mm(W), 27in/686mm(D)
- Nameplate : Standard
- Standard kVA : 112.5
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=1
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423123963
- Weight : 800
- Certification : CSA, UL