2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Schneider Electric
- Sub-Category:Molded Case
Description
QOB240GFI
QOB240GFI is a Square D 2 pole ground fault circuit breaker rated for 40 amps and 120/240 volts AC with bolt-on mounting.This Square D QOB240GFI circuit breaker provides ground fault protection with a 6mA trip sensitivity and a 10kA interrupt rating. It features a thermal magnetic trip unit and is designed for use in QO or NQOD panelboards. The breaker includes a Visi-Trip indicator for easy identification of tripped status and is UL listed and CSA approved.
- Key Specifications
- Amperage: 40 Amps
- Voltage: 120/240 VAC
- Poles: 2
- Mounting Type: Bolt-On
- Interrupt Rating: 10,000 AIC (10 kA)
- Trip Unit: Thermal Magnetic
- Ground Fault Trip Sensitivity: 6 mA
- Series/Frame: QOB
- Dimensions (H x W x D): Approx. 4.12" x 1.5" x 2.91"
- Certifications: UL Listed, CSA Approved
Specifications
- Part Number: QOB240GFI
- Manufacturer : Schneider Electric
- Brand : Square D
- Category : Circuit Breaker
- Item Subcategory : Molded Case
- Family : QOB Series
- Type : QOB
- Voltage : 120/240VAC
- Amperage : 40
- Phase : 1
- Poles : 2
- AIC rating : 10kA@240V
- Connection : Bolt-On
- Functions : LI - Long-Time and Instantaneous Trip
- Terminal Connection : Pressure Plate
- Frame Size : 100A/QO
- Temp Rating : -13‰ÛÒ158 å¡F (-25‰ÛÒ70 å¡C)
- MCM Size : Min. Wire Size 12 AWG (Al), 14 AWG (Cu) Max. Wire Size 4 AWG (Al), 6 AWG (Cu)
- Breaker Type : Ground Fault Circuit Interrupter (Class A - 5mA)
- Protection : Thermal Magnetic
Product Data
- UPC : 785901362951
- GTIN : 00785901362951
- Country of Origin : Mexico
- Dimensions : 4.1 in (105 mm) x 1.5 in (38 mm) x 2.9 in (74 mm) (Height x Width x Depth)
- Weight : 1.036
- Panel Type : QO Load Centers and NQ Panelboards
- Standards : CSA, UL Listed
- Certification : UL Listed
- Wire Size : AWG 14 to AWG 6, Copper, AWG 12 to AWG 4, Aluminum
You may also like