2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
MG3A1000SPSAHC0
MG3A1000SPSAHC0 is a 1000 kVA three-phase dry-type transformer by Hammond Power Solutions designed for medium voltage distribution applications.This transformer features a primary voltage of 4160V Delta and a secondary voltage of 600Y/347V, operating at 60 Hz frequency. It is part of the HPS Millennium G series, with a 220°C insulation temperature class and an enclosed NEMA 3R ventilated enclosure suitable for indoor or outdoor use. The unit is aluminum wound and built for reliable power distribution with a 2-year warranty.
- Key Specifications
- Power Rating: 1000 kVA
- Phase: 3-Phase
- Primary Voltage: 4160V Delta
- Secondary Voltage: 600Y/347V
- Frequency: 60 Hz
- Insulation Temperature Class: 220°C
- Enclosure Type: NEMA 3R ventilated
- Mounting Type: Floor mounted
- Winding Material: Aluminum
- Series: HPS Millennium G
- Warranty: 2 years
Specifications
- Part Number: MG3A1000SPSAHC0
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 4160D
- Primary Connection : Delta
- Primary FCAN (NPL) : 2x2.5%
- Primary FCBN (NPL) : 2x2.5%
- Secondary Voltage : 600Y/346
- Secondary Connection : Wye-N
- Material : Aluminum
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 1000
- Efficiency Regulation : DOE 2016 (US), NRCAN 2019 (Canada), NMX 2021 (Mexico)
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 64 dBA (IEEE C57.12.01)
- Impedance (Std) : 4% - 7.5%
- Secondary Termination (NPL) : Mounting Pads
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : DH10-N3R
- Enclosure Dimensions : 86in/2185mm(H), 78in/1982mm(W), 52in/1321mm(D)
- Nameplate : Standard
- Standard kVA : 1000
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423133955
- Weight : 7000
- Certification : CSA, UL
Documentation and Resources
You may also like