2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
MG3A0075SKSAGC0
MG3A0075SKSAGC0 is a 75 kVA three phase aluminum wound medium voltage distribution transformer with a 2400 Delta primary and 480Y/277 secondary, designed for reliable power distribution in commercial and industrial applications. This Hammond Power Solutions transformer features a heavy duty ventilated Type 3R enclosure, standard 220°C insulation system with a 150°C temperature rise, and is suitable for both floor and optional wall/ceiling mounting. The unit is engineered for durability and performance, with a 10 kV BIL rating and ANSI 61 Grey finish. It is UL Listed and CSA Certified, meeting North American efficiency standards.
- 75 kVA three phase aluminum wound transformer
- 2400 Delta primary voltage
- 480Y/277 secondary voltage
- 60 Hz frequency
- Type 3R heavy duty ventilated enclosure
- 220°C insulation system, 150°C temperature rise
- 10 kV BIL rating
- ANSI 61 Grey finish
- Floor mounting standard, wall/ceiling optional
- UL Listed
- CSA Certified
- Meets DOE 2016 and NRCan 2019 efficiency standards
Specifications
- Part Number: MG3A0075SKSAGC0
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 4160D
- Primary Connection : Delta
- Primary FCAN (NPL) : 2x2.5%
- Primary FCBN (NPL) : 2x2.5%
- Secondary Voltage : 480Y/277
- Secondary Connection : Wye-N
- Material : Aluminum
- Temperature Rise : 130°C
- Insulation Class : 200°C
- EKVA : 82.017
- Efficiency Regulation : DOE 2016 (US), NRCAN 2019 (Canada), NMX 2021 (Mexico)
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=1, lp=1.5)
- Sound Level : 50 dBA (IEEE C57.12.01)
- Impedance (Std) : 2.5% - 6.5%
- Secondary Termination (NPL) : Mechanical Lugs
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : DH4-N3R
- Enclosure Dimensions : 44.5in/1131mm(H), 31.5in/801mm(W), 29.5in/750mm(D)
- Nameplate : Standard
- Standard kVA : 75
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=1
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- Weight : 729
- Certification : CSA, UL
Documentation and Resources
You may also like
- Opens in a new window.