- Manufacturer:Hammond Power Solutions
Description
MG3A0030SKSCHC0
MG3A0030SKSCHC0 is a 30kVA three-phase dry type transformer from Hammond Power Solutions designed for medium voltage distribution applications.
This transformer features a primary voltage of 4160V delta and a secondary voltage of 480Y/277V, operating at 60 Hz frequency. It has a temperature rise rating of 130°C and is enclosed in a NEMA 3R type enclosure suitable for outdoor or harsh environments. The unit is copper wound and built to the MDT series specifications, providing reliable performance and durability for commercial and industrial power distribution needs.
- Power Rating: 30 kVA
- Phase: 3 Phase
- Primary Voltage: 4160V Delta
- Secondary Voltage: 480Y/277V
- Frequency: 60 Hz
- Temperature Rise: 130°C
- Enclosure Type: NEMA 3R
- Winding Material: Copper
- Transformer Type: Dry Type
- Series: MDT
At Essential Parts, we offer fast shipping, lowest price, and expert support to help you get the right product every time.
Specifications
- Part Number: MG3A0030SKSCHC0
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 4160D
- Primary Connection : Delta
- Primary FCAN (NPL) : 2x2.5%
- Primary FCBN (NPL) : 2x2.5%
- Secondary Voltage : 480Y/277
- Secondary Connection : Wye-N
- Temperature Rise : 130°C
- Insulation Class : 200°C
- EKVA : 32.8068
- Efficiency Regulation : DOE 2016 (US), NRCAN 2019 (Canada), NMX 2021 (Mexico)
- Seismic Compliance : OSHPD, IBC 2018 (Sds=2.0, z/h=1, lp=1.5)
- Sound Level : 45 dBA (IEEE C57.12.01)
- Impedance (Std) : 2.5% - 6.5%
- Secondary Termination (NPL) : Mechanical Lugs
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : DH2-N3R
- Enclosure Dimensions : 28.75in/731mm(H), 25.75in/655mm(W), 23.8in/605mm(D)
- Nameplate : Standard
- Standard kVA : 30
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : Yes
- Seismic IP : lp=1.5
- Seismic ZH : z/h=1
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No