2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Eaton
- Sub-Category:Molded Case
Description
FAZ-C40/2
FAZ-C40/2-NA is a 40 amp, 2-pole, C curve thermal magnetic circuit breaker designed for medium inrush current applications. It provides reliable branch circuit protection with a compact design.FAZ-C40/2-NA features a 10 kA interrupting rating at 277/480 VAC, suitable for industrial and commercial use. It mounts on a 35mm DIN rail and includes screw terminals for secure wiring. This UL 489 listed supplementary protector is ideal for protecting small transformers and pilot devices, with a trip type of 5-10X/n and frequency rating of 50-60 Hz.
- Key Specifications
- Amperage Rating: 40 A
- Voltage Rating: 277/480 VAC, 48/96 VDC
- Number of Poles: 2
- Trip Curve: C curve
- Trip Type: Thermal magnetic, 5-10X/n
- Interrupting Rating: 10 kAIC @ 277/480 VAC
- Mounting Type: 35mm DIN rail
- Terminals: Screw
- Certifications: UL 489 Listed, CSA Certified
- Frequency: 50-60 Hz
- Application: Medium inrush current protection
Specifications
- Part Number: FAZ-C40/2
- Manufacturer : Eaton
- Brand : Eaton
- Category : Circuit Breaker
- Item Subcategory : Molded Case
- Family : FAZ Series
- Type : FAZ
- Voltage : 480
- Amperage : 40
- Phase : 1
- Poles : 2
- AIC rating : 10kA@277/480V
- Connection : Feed-Thru
- Functions : LI - Long Time and Instantaneous
- Terminal Connection : Lug
- MCM Size : Min. Wire Size 18 AWG Max. Wire Size 4 AWG
- Protection : Thermal Magnetic
Product Data
- UPC : 01508278764
- GTIN : 04015082787646
- Country of Origin : Romania
- Dimensions : 1.38 in x 1.38 in x 1.5 in (Length/Depth x Height x Width)
- Weight : 0.53
- Standards : CSA C22.2 No. 235, IEC 60947-2, UL 1077
- Certification : CSA C22.2 No. 235, IEC 60947-2, UL 1077