2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
DM660NJC
DM660NJC is a three-phase drive isolation transformer rated 660 kVA with primary voltage of 575 delta and secondary voltage of 460Y, designed for industrial power distribution applications up to 600V class. This copper-wound transformer provides reliable isolation and voltage transformation for motor drives and other industrial equipment requiring stable power conditioning. The unit features floor mounting configuration and meets industry standards for short circuit withstand requirements per UL and CSA specifications. Key Specifications
- Part Number: DM660NJC
- Manufacturer: Hammond Power Solutions
- Capacity: 660 kVA
- Primary Voltage: 575 Delta
- Secondary Voltage: 460Y
- Phase: Three Phase
- Winding Material: Copper
- Mounting Type: Floor
- Case Style: NJ3
- Approximate Weight: 3250 lbs
- UL and CSA Certified
Specifications
- Part Number: DM660NJC
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 575D
- Primary Connection : Delta
- Secondary Voltage : 460Y/266
- Secondary Connection : Wye-N
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 660
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 62 dBA (NEMA ST-20)
- Impedance (Std) : 5.5% - 7.5%
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NJ3-N3R
- Enclosure Dimensions : 66in/1677mm(H), 51.5in/1309mm(W), 43.4in/1103mm(D)
- Nameplate : Standard
- Standard kVA : 660
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
- Primary FCAN (Std) : 2x2.5%
- Primary Termination (Std) : Mounting Pads
Product Data
- UPC : 803423004781
- GTIN : 00803423004781
- Weight : 3250
- Certification : CSA, UL
Documentation and Resources
You may also like
- Opens in a new window.