2 Year Warranty Guaranteed
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
DM275JH
DM275JH is a 275 kVA drive isolation transformer from Hammond Power Solutions designed for industrial applications requiring electrical isolation and reliable power conversion.
This transformer features a 460 VAC primary voltage and 400Y VAC secondary voltage with a 3-phase configuration. It is constructed with aluminum windings and a 220°C insulation system, suitable for 60 Hz operation. The unit includes lug/pad type connections and is designed for floor mounting. It provides electrical isolation between the incoming line and the SCR load, withstanding overcurrent conditions of 150% rated load for 60 seconds or 200% for 30 seconds. The enclosure is suitable for indoor/outdoor use with ANSI 61 UL 50 gray finish and includes a coil-mounted thermal warning switch.
- Power rating: 275 kVA
- Primary voltage: 460 VAC
- Secondary voltage: 400Y VAC
- Phase: 3-phase
- Frequency: 60 Hz
- Winding material: Aluminum
- Insulation temperature rating: 220°C
- Connection type: Lug/Pad
- Mounting type: Floor mount
- Overcurrent withstand: 150% rated load for 60 seconds, 200% for 30 seconds
- Enclosure: Indoor/Outdoor, ANSI 61 UL 50 gray finish
- Includes coil-mounted thermal warning switch
At Essential Parts, we offer fast shipping, lowest price, and expert support to help you get the right product every time.
Specifications
- Part Number: DM275JH
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 460D
- Primary Connection : Delta
- Primary FCAN (NPL) : 2x2.5%
- Primary FCBN (NPL) : 2x2.5%
- Secondary Voltage : 400Y/231
- Secondary Connection : Wye-N
- Material : Aluminum
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 275
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 55 dBA (NEMA ST-20)
- Impedance (Std) : 4% - 7%
- Secondary Termination (NPL) : Mounting Pads
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NJ1-N3R
- Enclosure Dimensions : 51.5in/1309mm(H), 39.5in/1004mm(W), 34in/864mm(D)
- Nameplate : Standard
- Standard kVA : 275
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423052768
- GTIN : 00803423052768
- Weight : 1400
- Certification : CSA, UL