2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
DM145NJC
Hammond Power Solutions DM145NJC is a three-phase general duty transformer designed for industrial power distribution applications. This unit features a 575V delta primary connection with ±5% FCAN/FCBN taps and delivers 460Y/266V secondary output through a wye-N configuration with mechanical lug terminations. The transformer is housed in a Type 3R/IP24 rated enclosure with ANSI 61 grey finish, measuring 41" H × 32" W × 25.5" D, and operates with 150°C temperature rise using 220°C insulation class materials. It complies with IBC 2018 seismic standards (Sds=2.0, z/h=0, lp=1.5) and NEMA ST-20 sound level requirements at 50 dBA, approved for installation in US and LATAM markets. Typical applications include industrial plants, manufacturing facilities, and commercial buildings requiring reliable three-phase power conversion. Key Features & Specifications
- Type: Three-Phase General Duty Transformer
- Primary Voltage: 575V Delta
- Secondary Voltage: 460Y/266V Wye-N
- kVA Rating: 145 kVA
- Frequency: 60 Hz
- Impedance: 3% - 6%
- Temperature Rise: 150°C
- Insulation Class: 220°C
- Enclosure: Type 3R/IP24
- Dimensions: 41" H × 32" W × 25.5" D
- Sound Level: 50 dBA (NEMA ST-20)
- Seismic Compliance: IBC 2018
Specifications
- Part Number: DM145NJC
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 575D
- Primary Connection : Delta
- Primary FCAN (NPL) : 1x5%
- Primary FCBN (NPL) : 1x5%
- Secondary Voltage : 460Y/266
- Secondary Connection : Wye-N
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 145
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 50 dBA (NEMA ST-20)
- Impedance (Std) : 3% - 6%
- Secondary Termination (NPL) : Mechanical Lugs
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NH4-N3R
- Enclosure Dimensions : 41in/1042mm(H), 32in/813mm(W), 25.5in/648mm(D)
- Nameplate : Standard
- Standard kVA : 145
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423003944
- GTIN : 00803423003944
- Weight : 965
- Certification : CSA, UL
Documentation and Resources
You may also like
- Opens in a new window.