2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
DM118JHC
DM118JHC is a three phase drive isolation transformer from Hammond Power Solutions with a power rating of 118 kVA and primary voltage of 460 VAC and secondary voltage of 400 VAC.DM118JHC features a dry type construction designed for floor mounting, meeting UL and CSA short circuit withstand requirements. It is part of the DM Series known for reliable isolation and protection in industrial applications. This transformer uses copper windings and has a typical impedance of 3 to 6%.
- Power rating: 118 kVA
- Primary voltage: 460 VAC
- Secondary voltage: 400 VAC
- Three phase configuration
- Dry type transformer
- Floor mounting only
- UL and CSA short circuit withstand certified
- Typical impedance: 3 to 6%
- Copper windings
- Part of DM Series
Specifications
- Part Number: DM118JHC
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 460D
- Primary Connection : Delta
- Primary FCAN (NPL) : 1x5%
- Primary FCBN (NPL) : 1x5%
- Secondary Voltage : 400Y/231
- Secondary Connection : Wye-N
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 118
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 50 dBA (NEMA ST-20)
- Impedance (Std) : 3% - 6%
- Secondary Termination (NPL) : Mechanical Lugs
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NH3-N3R
- Enclosure Dimensions : 38in/966mm(H), 26in/661mm(W), 21in/534mm(D)
- Nameplate : Standard
- Standard kVA : 118
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423052539
- Weight : 790
- Certification : CSA, UL
Documentation and Resources
You may also like
- Opens in a new window.