DM118JC is a three-phase drive isolation transformer rated at 118 kVA with a primary voltage of 460 Delta V AC and secondary voltage of 230Y V AC, designed for industrial power distribution and motor drive applications. This non-efficient standard transformer features a 220 degree C insulation system with a 150 degree C rise, providing reliable performance in demanding environments. The unit comes standard with an indoor/outdoor NEMA 3R enclosure and includes a coil-mounted thermal warning switch for added protection. Key Specifications
- Power Rating: 118 kVA
- Primary Voltage: 460 Delta V AC
- Secondary Voltage: 230Y V AC
- Phase: 3
- Frequency: 60 Hz
- Insulation Class: 220 degree C
- Temperature Rise: 150 degree C
- Enclosure Type: NEMA 3R
- Mounting Type: Floor
- Connection Type: Lug/Pad
- Certifications: UL, CSA
- Dimensions: 21 in L x 26 in W x 38 in H
Specifications
- Part Number: DM118JC
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 460D
- Primary Connection : Delta
- Primary FCAN (NPL) : 1x5%
- Primary FCBN (NPL) : 1x5%
- Secondary Voltage : 230Y/133
- Secondary Connection : Wye-N
- Material : Aluminum
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 118
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 50 dBA (NEMA ST-20)
- Impedance (Std) : 3% - 6%
- Secondary Termination (NPL) : Mounting Pads
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NH3-N3R
- Enclosure Dimensions : 38in/966mm(H), 26in/661mm(W), 21in/534mm(D)
- Nameplate : Standard
- Standard kVA : 118
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423003753
- GTIN : 00803423003753
- Weight : 735
- Certification : CSA, UL