DM027JJCN - Hammond Power Solutions 27 kVA 3-Phase 460V Drive Isolation Transformer Copper Wound

Authorized Distributor - Hammond
Save $628.67
SKU: DM027JJCN-New

Condition: New
Price:
Sale price$3,451.33 Regular price$4,080.00
Stock:
Low inventory, please call for stock check
Factory Lead Time: 33-40 Working Days - (Non-Returnable) business days. Ships based on manufacturer availability when out of stock. All factory-ordered products are non-cancelable and non-returnable.

💡 Important Notice for Hammond Transformers

Hammond Transformer products are Non-Cancellable and Non-Returnable.

Same-Day Shipping

Most items ship same-day if ordered by 12:30 PM PST.

2 Year Warranty Guaranteed

All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.

Product Questions? Contact Us

Product Info

Description

DM027JJCN


DM027JJCN is a 3-phase drive isolation transformer from Hammond Power Solutions designed for industrial power distribution applications.

This transformer features a 27 kVA copper-wound construction with a primary and secondary voltage rating of 460 volts. It operates at 60 Hz frequency and is built with a 220°C insulation system (150°C rise), ensuring reliable performance in demanding environments. The unit is suitable for drive isolation and general duty use, providing robust electrical isolation and voltage transformation.

  • Power rating: 27 kVA
  • Phase: 3-phase
  • Primary voltage: 460V Delta
  • Secondary voltage: 460V Wye
  • Frequency: 60 Hz
  • Insulation system: 220°C (150°C rise)
  • Winding material: Copper
  • Application: Drive isolation transformer

At Essential Parts, we offer fast shipping, lowest price, and expert support to help you get the right product every time.


Specifications

  • Part Number: DM027JJCN
  • Manufacturer : Hammond Power Solutions
  • Brand : Hammond Power Solutions
  • Category : Transformer
  • Phase : 3
  • Enclosure Grade : Standard
  • Duty : General Duty
  • Frequency : 60Hz
  • Primary Voltage : 460D
  • Primary Connection : Delta
  • Primary FCAN (NPL) : 1x5%
  • Primary FCBN (NPL) : 1x5%
  • Secondary Voltage : 460Y/266
  • Secondary Connection : Wye-N
  • Temperature Rise : 130°C
  • Insulation Class : 200°C
  • EKVA : 29.5261
  • Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
  • Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
  • Sound Level : 45 dBA (NEMA ST-20)
  • Impedance (Std) : 3% - 6%
  • Secondary Termination (NPL) : Mechanical Lugs
  • Enclosure Type : Type 3R / IP24
  • Enclosure Finish : ANSI 61 Grey, UL50
  • Enclosure PN (NPL) : NH6-N3R
  • Enclosure Dimensions : 28.75in/731mm(H), 23.9in/608mm(W), 25in/635mm(D)
  • Nameplate : Standard
  • Standard kVA : 27
  • Vector Configuration : Dyn1 (-30°)
  • Seismic Standard Value : IBC 2018
  • OSHPD : No
  • Seismic IP : lp=1.5
  • Seismic ZH : z/h=0
  • Seismic SDS Value : Sds=2.0
  • Enclosure IR Window : No

Product Data

  • UPC : 803423033651
  • GTIN : 00803423033651
  • Weight : 305
  • Certification : CSA, UL

Documentation and Resources