DM014NNCN - Hammond Power Solutions 3-Phase 14 kVA Drive Isolation Transformer 575V Primary 575V Secondary Copper Wound

Authorized Distributor - Hammond
Save $354.88
SKU: DM014NNCN-New

Condition: New
Price:
Sale price$1,935.12 Regular price$2,290.00
Stock:
Low inventory, please call for stock check
This ships in 3-5 business days

💡 Important Notice for Hammond Transformers

Hammond Transformer products are Non-Cancellable and Non-Returnable.

Same-Day Shipping

Most items ship same-day if ordered by 12:30 PM PST.

2 Year Warranty Guaranteed

All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.

Product Questions? Contact Us

Product Info

Description

DM014NNCN


DM014NNCN is a three-phase drive isolation transformer designed for industrial applications requiring reliable power isolation and voltage transformation. This Hammond Power Solutions transformer features a copper wound coil and is rated for 14 kVA output with a 575V primary and 575V secondary voltage, making it suitable for drive systems and other demanding environments. The DM014NNCN is engineered for durability and performance, providing effective electrical isolation and noise reduction for sensitive equipment. Its robust construction ensures stable operation under continuous load conditions, supporting efficient power distribution in industrial settings.
  • 3-Phase configuration
  • 14 kVA output rating
  • 575V primary voltage
  • 575V secondary voltage
  • Copper wound coil
  • Drive isolation transformer
  • 600V class
  • Three-phase delta primary
  • Three-phase wye secondary
  • Designed for industrial applications
  • Weight: 4.54 kg
At Essential Parts, we offer fast shipping, lowest price, and expert support to help you get the right product every time.

Specifications

  • Part Number: DM014NNCN
  • Manufacturer : Hammond Power Solutions
  • Brand : Hammond Power Solutions
  • Category : Transformer
  • Phase : 3
  • Enclosure Grade : Standard
  • Duty : General Duty
  • Frequency : 60Hz
  • Primary Voltage : 575D
  • Primary Connection : Delta
  • Primary FCAN (NPL) : 1x5%
  • Primary FCBN (NPL) : 1x5%
  • Secondary Voltage : 575Y/332
  • Secondary Connection : Wye-N
  • Temperature Rise : 130°C
  • Insulation Class : 200°C
  • EKVA : 15.3098
  • Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
  • Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
  • Sound Level : 45 dBA (NEMA ST-20)
  • Impedance (Std) : 3% - 6%
  • Secondary Termination (NPL) : Terminal Block
  • Enclosure Type : Type 3R / IP24
  • Enclosure Finish : ANSI 61 Grey, UL50
  • Enclosure PN (NPL) : NH5-N3R
  • Enclosure Dimensions : 21.5in/547mm(H), 19.38in/493mm(W), 20.2in/514mm(D)
  • Nameplate : Standard
  • Standard kVA : 14
  • Vector Configuration : Dyn1 (-30°)
  • Seismic Standard Value : IBC 2018
  • OSHPD : No
  • Seismic IP : lp=1.5
  • Seismic ZH : z/h=0
  • Seismic SDS Value : Sds=2.0
  • Enclosure IR Window : No

Product Data

  • UPC : 803423033569
  • GTIN : 00803423033569
  • Weight : 185
  • Certification : CSA, UL