2 Year Warranty Guaranteed
All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.
Product Questions? Contact Us
Product Info
- Manufacturer:Hammond Power Solutions
Description
DM014KK
DM014KK is a 14 kVA 3-phase drive isolation transformer from Hammond Power Solutions designed for industrial power applications.
This transformer features a 480 VAC delta primary voltage and a 480Y/277 VAC wye secondary voltage with aluminum windings. It operates at 60 Hz frequency and is built with a 220°C insulation class for reliable thermal performance. The unit supports lug/pad connections and is suitable for floor or wall mounting. It is engineered to meet UL and CSA short circuit withstand requirements and provides a sound level of 45 dBA, complying with NEMA ST-20 standards.
- Power Rating: 14 kVA
- Phase: 3-Phase
- Primary Voltage: 480 VAC Delta
- Secondary Voltage: 480Y/277 VAC Wye
- Frequency: 60 Hz
- Winding Material: Aluminum
- Insulation Class: 220°C
- Mounting Type: Floor or Wall
- Connection Type: Lug/Pad
- Sound Level: 45 dBA (NEMA ST-20)
- Short Circuit Withstand: UL and CSA Compliant
At Essential Parts, we offer fast shipping, lowest price, and expert support to help you get the right product every time.
Specifications
- Part Number: DM014KK
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 480D
- Primary Connection : Delta
- Primary FCAN (NPL) : 1x5%
- Primary FCBN (NPL) : 1x5%
- Secondary Voltage : 480Y/277
- Secondary Connection : Wye-N
- Material : Aluminum
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 14
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 45 dBA (NEMA ST-20)
- Impedance (Std) : 3% - 6%
- Secondary Termination (NPL) : Mechanical Lugs
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NH5-N3R
- Enclosure Dimensions : 21.5in/547mm(H), 19.38in/493mm(W), 20.2in/514mm(D)
- Nameplate : Standard
- Standard kVA : 14
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423052003
- GTIN : 00803423052003
- Weight : 195
- Certification : CSA, UL
Documentation and Resources
You may also like
- Opens in a new window.