Product Info
- Manufacturer:Hammond Power Solutions
Description
DM014JC
Hammond Power Solutions DM014JC is a three-phase general duty transformer designed for industrial power distribution applications. This 14 kVA unit operates at 60Hz with a primary voltage of 460V Delta and secondary voltage of 230Y/133V Wye-N, featuring aluminum windings rated for 150°C temperature rise with 220°C insulation class. The transformer is housed in a Type 3R/IP24 enclosure with ANSI 61 Grey finish, measuring 21.5 inches high by 19.38 inches wide by 20.2 inches deep, and produces a sound level of 45 dBA. It complies with IBC 2018 seismic standards (Sds=2.0, z/h=0, lp=1.5) and is approved for installation in US and LATAM markets. Typical applications include industrial machinery, manufacturing equipment, and commercial power systems requiring reliable voltage transformation. Key Features & Specifications
- Type: Three-phase general duty transformer
- Voltage: Primary 460V Delta, Secondary 230Y/133V Wye-N
- Current: 14 kVA capacity
- Frequency: 60Hz
- Material: Aluminum windings
- Temperature Rise: 150°C
- Insulation Class: 220°C
- Impedance: 3% - 6% standard
- Enclosure: Type 3R/IP24, ANSI 61 Grey
- Dimensions: 21.5" H × 19.38" W × 20.2" D
- Sound Level: 45 dBA (NEMA ST-20)
- Seismic Compliance: IBC 2018 (Sds=2.0)
- Terminations: Mechanical lugs (primary and secondary)
- Vector Configuration: Dyn1 (-30°)
Specifications
- Part Number: DM014JC
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 460D
- Primary Connection : Delta
- Primary FCAN (NPL) : 1x5%
- Primary FCBN (NPL) : 1x5%
- Secondary Voltage : 230Y/133
- Secondary Connection : Wye-N
- Material : Aluminum
- Temperature Rise : 150°C
- Insulation Class : 220°C
- EKVA : 14
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 45 dBA (NEMA ST-20)
- Impedance (Std) : 3% - 6%
- Secondary Termination (NPL) : Mechanical Lugs
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NH5-N3R
- Enclosure Dimensions : 21.5in/547mm(H), 19.38in/493mm(W), 20.2in/514mm(D)
- Nameplate : Standard
- Standard kVA : 14
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
- Primary Termination (Std) : Mechanical Lugs
Product Data
- UPC : 803423002671
- GTIN : 00803423002671
- Weight : 190
- Certification : CSA, UL