Product Info
- Manufacturer:Hammond Power Solutions
Description
DM011NJCN
DM011NJCN is a three-phase drive isolation transformer rated at 11 kVA with 575 volts delta primary and 460 volts wye secondary, designed for industrial drive applications and motor control systems. This copper-wound transformer features a 600V class rating and is engineered to provide reliable voltage conversion and isolation in demanding industrial environments. The unit meets UL and CSA short circuit withstand requirements and complies with IBC 2018 seismic standards (Sds=2.0) while maintaining a low 45 dBA sound level per NEMA ST-20 requirements.
- Rated Capacity: 11 kVA
- Primary Voltage: 575V Delta
- Secondary Voltage: 460V Wye
- Phase Configuration: Three-Phase
- Frequency: 60 Hz
- Conductor Material: Copper Wound
- Insulation System: 220°C (150°C rise)
- Impedance: Typically 3 to 6%
- Mounting Type: Floor or Wall
- Short Circuit Withstand: Meets UL and CSA requirements
- Seismic Compliance: IBC 2018 (Sds=2.0)
- Sound Level: 45 dBA per NEMA ST-20
Specifications
- Part Number: DM011NJCN
- Manufacturer : Hammond Power Solutions
- Brand : Hammond Power Solutions
- Category : Transformer
- Phase : 3
- Enclosure Grade : Standard
- Duty : General Duty
- Frequency : 60Hz
- Primary Voltage : 575D
- Primary Connection : Delta
- Primary FCAN (NPL) : 1x5%
- Primary FCBN (NPL) : 1x5%
- Secondary Voltage : 460Y/266
- Secondary Connection : Wye-N
- Temperature Rise : 130°C
- Insulation Class : 200°C
- EKVA : 12.0292
- Efficiency Regulation : No Efficiency Specification; approved for installation in US and LATAM
- Seismic Compliance : IBC 2018 (Sds=2.0, z/h=0, lp=1.5)
- Sound Level : 45 dBA (NEMA ST-20)
- Impedance (Std) : 3% - 6%
- Secondary Termination (NPL) : Terminal Block
- Enclosure Type : Type 3R / IP24
- Enclosure Finish : ANSI 61 Grey, UL50
- Enclosure PN (NPL) : NH5-N3R
- Enclosure Dimensions : 21.5in/547mm(H), 19.38in/493mm(W), 20.2in/514mm(D)
- Nameplate : Standard
- Standard kVA : 11
- Vector Configuration : Dyn1 (-30°)
- Seismic Standard Value : IBC 2018
- OSHPD : No
- Seismic IP : lp=1.5
- Seismic ZH : z/h=0
- Seismic SDS Value : Sds=2.0
- Enclosure IR Window : No
Product Data
- UPC : 803423033491
- GTIN : 00803423033491
- Weight : 185
- Certification : CSA, UL
Documentation and Resources