BDA24050Y1 - Square D 50A 2 Pole 480Y/277VAC I-Line Thermal Magnetic Circuit Breaker

Save $208.69
SKU: BDA24050Y1-New

Condition: New
Price:
Sale price$505.31 Regular price$714.00
Stock:
Low inventory, please call for stock check

Same-Day Shipping

Most items ship same-day if ordered by 12:30 PM PST.

2 Year Warranty Guaranteed

All items both Re-Certified, and New sold by Essential Electric include a 30 day return policy and a 2-year full warranty. This means that they are guaranteed to be free from defects for a full 2 years from the date that the product was shipped from our warehouse.

Product Questions? Contact Us

Product Info

Description

BDA24050Y1


BDA24050Y1 is a 2 pole, 50 amp thermal magnetic molded case circuit breaker designed for 480Y/277VAC applications with I-Line style plug-in mounting.The Square D BDA24050Y1 features long time and instantaneous trip functions, an 18kA interrupting rating at 480V, and is part of the BDA series frame. It supports line and load lug terminal connections and is suitable for industrial control panels and electrical distribution equipment.
    Key Specifications
    • Amperage: 50 Amps
    • Voltage Rating: 480Y/277VAC
    • Number of Poles: 2
    • Interrupting Rating: 18kA at 480V AC
    • Mounting Type: I-Line Style Plug-In
    • Trip Unit: Thermal Magnetic with Long Time and Instantaneous Trip
    • Frame/Series: BDA
    • Terminal Connection: Line and Load Lug
    • Wire Gauge: AWG 14 to AWG 2/0 Aluminum/Copper
    • Certifications: UL 489, CSA, CE, NEMA, IEC, RoHS
    • Operating Temperature: -13 to 158°F
    • Phase: Single
At Essential Parts, we offer fast shipping, lowest price, and expert support to help you get the right product every time.

Specifications

  • Part Number: BDA24050Y1
  • Manufacturer : Schneider Electric
  • Brand : Square D
  • Category : Circuit Breaker
  • Item Subcategory : Molded Case
  • Family : PowerPact B
  • Type : BDA
  • Voltage : 480
  • Amperage : 50
  • Phase : 1
  • Poles : 2
  • AIC rating : 18@480VAC
  • Connection : I-Line
  • Functions : Long Time and Instantaneous Trip
  • Terminal Connection : Al Mechanical Lug OFF End, I-Line ON End
  • Frame Size : 125A/BD
  • Temp Rating : -13–158 °F (-25–70 °C)
  • MCM Size : Min. Wire Size 14 AWG Max. Wire Size 2 AWG
  • Breaker Type : Standard
  • Protection : Thermal Magnetic
  • Phase Connection : AB

Product Data

  • UPC : 606481151851
  • Country of Origin : Mexico
  • Dimensions : 5.4 in (137 mm) x 2.1 in (54 mm) x 3.5 in (89 mm) (Height x Width x Depth)
  • Weight : 2.91
  • Panel Type : Electrical Distribution Equipment, Industrial Control Panels
  • Standards : EN/IEC 60947-2, GB 14048.2, CSA C22.2 No 5, NEMA AB1, EN/IEC 60947-5-1, NMX J-266, UL 489
  • Certification : UL, IEC, CCC, EAC, CSA, NOM
  • Wire Size : AWG 14...AWG 2/0 aluminium/copper



ask us a question logo