{"product_id":"tx2a0030hckf5","title":"Hammond Power Solutions TX2A0030HCKF5 - 3-Phase Transformer 30 kVA (Type 4\/IP66)","description":" \t\t\t\t\t\t\t\t\t\t\u003ch2\u003eTX2A0030HCKF5\u003c\/h2\u003e                                         \u003cbr\u003e \t\t\t\t\t\t\t\t\t\tHammond Power Solutions TX2A0030HCKF5 is a three-phase transformer designed for industrial power distribution applications. This 30 kVA unit features a 400V delta primary configuration and delivers 230Y\/133V secondary output with copper windings rated for 115Â°C temperature rise and 180Â°C insulation class. The transformer is housed in a Type 4\/IP66 rated enclosure with ANSI 61 grey finish, measuring 21.88 inches high by 26.13 inches wide by 19.75 inches deep, and operates at 50\/60 Hz with 2-6.5% impedance and 50 dBA sound level. It complies with OSHPD and IBC 2018 seismic standards (Sds=2.0, z\/h=1, lp=1.5) and carries UL50 certification for general duty applications including some hazardous locations and marine ABS duty. Typical applications include industrial facilities requiring reliable power conversion with seismic resilience and environmental protection.      \u003cb\u003eKey Features \u0026amp; Specifications\u003c\/b\u003e  \u003cul\u003e \u003cli\u003eType: Three-Phase Transformer\u003c\/li\u003e \u003cli\u003eVoltage: 400V Delta Primary, 230Y\/133V Secondary\u003c\/li\u003e \u003cli\u003eCurrent: 30 kVA Capacity\u003c\/li\u003e \u003cli\u003eFrequency: 50\/60 Hz\u003c\/li\u003e \u003cli\u003eImpedance: 2% - 6.5%\u003c\/li\u003e \u003cli\u003eTemperature Rise: 115Â°C\u003c\/li\u003e \u003cli\u003eInsulation Class: 180Â°C\u003c\/li\u003e \u003cli\u003eEnclosure: Type 4 \/ IP66\u003c\/li\u003e \u003cli\u003eSound Level: 50 dBA\u003c\/li\u003e \u003cli\u003eSeismic Compliance: OSHPD, IBC 2018\u003c\/li\u003e \u003cli\u003eDimensions: 21.88\" H Ã— 26.13\" W Ã— 19.75\" D\u003c\/li\u003e \u003cli\u003eWeight: 595 lb\u003c\/li\u003e \u003c\/ul\u003e \t\t\t\t\t\t\t\t\t\t\u003cbr\u003e                                          \t\t\t\t\t\t\t\t\t\t\u003ch3\u003e\u003cb\u003eSpecifications\u003c\/b\u003e\u003c\/h3\u003e \t\t\t\t\t\t\t\t\t\t\u003cul\u003e \t\t\t\t\t\t\t\t\t\t\t\u003cli\u003ePart Number: TX2A0030HCKF5\u003c\/li\u003e                                             \u003cli\u003eManufacturer : Hammond Power Solutions\u003c\/li\u003e\n\u003cli\u003eBrand : Hammond Power Solutions\u003c\/li\u003e\n\u003cli\u003eCategory : Transformer\u003c\/li\u003e\n\u003cli\u003ePhase : 3\u003c\/li\u003e\n\u003cli\u003eEnclosure Grade : Standard\u003c\/li\u003e\n\u003cli\u003eDuty : General Duty (Suitable For Some Hazardous Locations and Marine ABS Duty)\u003c\/li\u003e\n\u003cli\u003eFrequency : 50\/60Hz\u003c\/li\u003e\n\u003cli\u003ePrimary Voltage : 400D\u003c\/li\u003e\n\u003cli\u003ePrimary Connection : Delta\u003c\/li\u003e\n\u003cli\u003eSecondary Voltage : 230Y\/133\u003c\/li\u003e\n\u003cli\u003eSecondary Connection : Wye-N\u003c\/li\u003e\n\u003cli\u003eMaterial : Copper\u003c\/li\u003e\n\u003cli\u003eTemperature Rise : 115Â°C\u003c\/li\u003e\n\u003cli\u003eInsulation Class : 180Â°C\u003c\/li\u003e\n\u003cli\u003eEKVA : 30\u003c\/li\u003e\n\u003cli\u003eEfficiency Regulation : No Efficiency Specification\u003c\/li\u003e\n\u003cli\u003eSeismic Compliance : OSHPD, IBC 2018 (Sds=2.0, z\/h=1, lp=1.5)\u003c\/li\u003e\n\u003cli\u003eSound Level : 50dBA (NEMA ST-20)\u003c\/li\u003e\n\u003cli\u003eImpedance (Std) : 2% - 6.5%\u003c\/li\u003e\n\u003cli\u003eEnclosure Type : Type 4 \/ IP66\u003c\/li\u003e\n\u003cli\u003eEnclosure Finish : ANSI 61 Grey, UL50\u003c\/li\u003e\n\u003cli\u003eEnclosure Dimensions : 21.88in\/556mm(H), 26.13in\/664mm(W), 19.75in\/502mm(D)\u003c\/li\u003e\n\u003cli\u003eElectrostatic Shield : Single\u003c\/li\u003e\n\u003cli\u003eNameplate : Standard\u003c\/li\u003e\n\u003cli\u003eStandard kVA : 30\u003c\/li\u003e\n\u003cli\u003eVector Configuration : Dyn1 (-30Â°)\u003c\/li\u003e\n\u003cli\u003eSeismic Standard Value : IBC 2018\u003c\/li\u003e\n\u003cli\u003eOSHPD : Yes\u003c\/li\u003e\n\u003cli\u003eSeismic IP : lp=1.5\u003c\/li\u003e\n\u003cli\u003eSeismic ZH : z\/h=1\u003c\/li\u003e\n\u003cli\u003eSeismic SDS Value : Sds=2.0\u003c\/li\u003e\n\u003cli\u003eEnclosure IR Window : No\u003c\/li\u003e\n\u003cli\u003ePrimary FCAN (Std) : 2x2.5%\u003c\/li\u003e\n\u003cli\u003ePrimary Termination (Std) : Mounting Pads\u003c\/li\u003e \t\t\t\t\t\t\t\t\t\t\u003c\/ul\u003e                                         \u003cbr\u003e                                         \u003ch3\u003e\u003cb\u003eProduct Data\u003c\/b\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eUPC : 803423168445\u003c\/li\u003e\n\u003cli\u003eWeight : 5.19 \u003c\/li\u003e\n\u003cli\u003eCertification : ABS, ATEX, IECEx and UKEx (Class I, Zone 2, Group IIC, T3 Hazardous Location)\u003c\/li\u003e\n\u003c\/ul\u003e                                         \u003cbr\u003e                                         \u003ch3\u003e\u003cb\u003eDocumentation and Resources\u003c\/b\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/engprd01.hammondpowersolutions.com\/info\/en\/pn\/TX2A0030HCKF5\" target=\"_blank\"\u003eEngineering Drawing (PDF) \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/documents.hammondpowersolutions.com\/documents\/Literature\/Low_Voltage_Distribution_(Encapsulated_and_Ventilated)_Brochures\/HPS-Titan-Series-Encapsulated-Transformer-for-Harsh-Environments-Brochure.pdf\" target=\"_blank\"\u003eBrochure \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/www.youtube.com\/@HammondPowerSolutionsIncHPS\/videos\" target=\"_blank\"\u003eHammond Product Application Videos \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/americas.hammondpowersolutions.com\/resources\/\" target=\"_blank\"\u003eFrequently Asked Questions \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"http:\/\/www.hammondpowersolutions.com\/en\/Resources\/categories\/troubleshooting\/\" target=\"_blank\"\u003eTroubleshooting Guide \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/engprd01.hammondpowersolutions.com\/encl\/pn\/DQT6-N4\/pdf\" target=\"_blank\"\u003eEnclosure CAD Drawing (PDF) \u003c\/a\u003e\u003c\/li\u003e\n\u003c\/ul\u003e ","brand":"Hammond Power Solutions","offers":[{"title":"New","offer_id":62209329627295,"sku":"TX2A0030HCKF5-New","price":11870.23,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0500\/2349\/7887\/files\/hammond-power-solutions-transformer-new-hammond-power-solutions-tx2a0030hckf5-3-phase-transformer-30-kva-type-4-ip66-53687944085663.jpg?v=1766010937","url":"https:\/\/essentialparts.com\/products\/tx2a0030hckf5","provider":"Essential Electric Supply","version":"1.0","type":"link"}