{"product_id":"tx2a0015khkf","title":"Hammond Power Solutions TX2A0015KHKF - 3-Phase Transformer 15kVA 480D-400Y\/231V","description":" \t\t\t\t\t\t\t\t\t\t\u003ch2\u003eTX2A0015KHKF\u003c\/h2\u003e                                         \u003cbr\u003e \t\t\t\t\t\t\t\t\t\tHammond Power Solutions TX2A0015KHKF is a three-phase transformer designed for industrial power distribution applications. This 15 kVA unit operates at 480V delta primary to 400Y\/231V secondary wye-n configuration with 60Hz frequency and features copper windings rated for 115Â°C temperature rise with 180Â°C insulation class. The transformer is housed in a Type 4\/IP66 enclosure with ANSI 61 grey finish, measuring 17.25\" H Ã— 22.38\" W Ã— 13.89\" D, and maintains a low 50 dBA sound level while providing 2%-6.5% impedance with single electrostatic shielding. It meets OSHPD and IBC 2018 seismic standards (Sds=2.0, z\/h=1, lp=1.5) with Dyn1 vector configuration and is suitable for general duty applications including some hazardous locations and marine ABS duty environments. Typical applications include industrial machinery, manufacturing facilities, and commercial power systems requiring reliable three-phase power conversion.      \u003cb\u003eKey Features \u0026amp; Specifications\u003c\/b\u003e  \u003cul\u003e \u003cli\u003eType: Three-Phase Transformer\u003c\/li\u003e \u003cli\u003eVoltage: 480V Delta Primary, 400Y\/231V Secondary\u003c\/li\u003e \u003cli\u003eCurrent: 15 kVA Capacity\u003c\/li\u003e \u003cli\u003eFrequency: 60Hz\u003c\/li\u003e \u003cli\u003eImpedance: 2% - 6.5%\u003c\/li\u003e \u003cli\u003eTemperature Rise: 115Â°C\u003c\/li\u003e \u003cli\u003eInsulation Class: 180Â°C\u003c\/li\u003e \u003cli\u003eEnclosure: Type 4 \/ IP66\u003c\/li\u003e \u003cli\u003eSound Level: 50 dBA\u003c\/li\u003e \u003cli\u003eSeismic Compliance: OSHPD, IBC 2018\u003c\/li\u003e \u003cli\u003eDimensions: 17.25\" H Ã— 22.38\" W Ã— 13.89\" D\u003c\/li\u003e \u003cli\u003eMaterial: Copper Windings\u003c\/li\u003e \u003cli\u003eVector Configuration: Dyn1 (-30Â°)\u003c\/li\u003e \u003c\/ul\u003e \t\t\t\t\t\t\t\t\t\t\u003cbr\u003e                                          \t\t\t\t\t\t\t\t\t\t\u003ch3\u003e\u003cb\u003eSpecifications\u003c\/b\u003e\u003c\/h3\u003e \t\t\t\t\t\t\t\t\t\t\u003cul\u003e \t\t\t\t\t\t\t\t\t\t\t\u003cli\u003ePart Number: TX2A0015KHKF\u003c\/li\u003e                                             \u003cli\u003eManufacturer : Hammond Power Solutions\u003c\/li\u003e\n\u003cli\u003eBrand : Hammond Power Solutions\u003c\/li\u003e\n\u003cli\u003eCategory : Transformer\u003c\/li\u003e\n\u003cli\u003ePhase : 3\u003c\/li\u003e\n\u003cli\u003eEnclosure Grade : Standard\u003c\/li\u003e\n\u003cli\u003eDuty : General Duty (Suitable For Some Hazardous Locations and Marine ABS Duty)\u003c\/li\u003e\n\u003cli\u003eFrequency : 60Hz\u003c\/li\u003e\n\u003cli\u003ePrimary Voltage : 480D\u003c\/li\u003e\n\u003cli\u003ePrimary Connection : Delta\u003c\/li\u003e\n\u003cli\u003eSecondary Voltage : 400Y\/231\u003c\/li\u003e\n\u003cli\u003eSecondary Connection : Wye-N\u003c\/li\u003e\n\u003cli\u003eMaterial : Copper\u003c\/li\u003e\n\u003cli\u003eTemperature Rise : 115Â°C\u003c\/li\u003e\n\u003cli\u003eInsulation Class : 180Â°C\u003c\/li\u003e\n\u003cli\u003eEKVA : 15\u003c\/li\u003e\n\u003cli\u003eEfficiency Regulation : No Efficiency Specification\u003c\/li\u003e\n\u003cli\u003eSeismic Compliance : OSHPD, IBC 2018 (Sds=2.0, z\/h=1, lp=1.5)\u003c\/li\u003e\n\u003cli\u003eSound Level : 50dBA (NEMA ST-20)\u003c\/li\u003e\n\u003cli\u003eImpedance (Std) : 2% - 6.5%\u003c\/li\u003e\n\u003cli\u003eEnclosure Type : Type 4 \/ IP66\u003c\/li\u003e\n\u003cli\u003eEnclosure Finish : ANSI 61 Grey, UL50\u003c\/li\u003e\n\u003cli\u003eEnclosure Dimensions : 17.25in\/439mm(H), 22.38in\/569mm(W), 13.89in\/353mm(D)\u003c\/li\u003e\n\u003cli\u003eElectrostatic Shield : Single\u003c\/li\u003e\n\u003cli\u003eNameplate : Standard\u003c\/li\u003e\n\u003cli\u003eStandard kVA : 15\u003c\/li\u003e\n\u003cli\u003eVector Configuration : Dyn1 (-30Â°)\u003c\/li\u003e\n\u003cli\u003eSeismic Standard Value : IBC 2018\u003c\/li\u003e\n\u003cli\u003eOSHPD : Yes\u003c\/li\u003e\n\u003cli\u003eSeismic IP : lp=1.5\u003c\/li\u003e\n\u003cli\u003eSeismic ZH : z\/h=1\u003c\/li\u003e\n\u003cli\u003eSeismic SDS Value : Sds=2.0\u003c\/li\u003e\n\u003cli\u003eEnclosure IR Window : No\u003c\/li\u003e\n\u003cli\u003ePrimary FCAN (Std) : 2x2.5%\u003c\/li\u003e\n\u003cli\u003ePrimary Termination (Std) : Wire Leads\u003c\/li\u003e \t\t\t\t\t\t\t\t\t\t\u003c\/ul\u003e                                         \u003cbr\u003e                                         \u003ch3\u003e\u003cb\u003eProduct Data\u003c\/b\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eUPC : 803423168421\u003c\/li\u003e\n\u003cli\u003eWeight : 5.19 \u003c\/li\u003e\n\u003cli\u003eCertification : ABS, ATEX, IECEx and UKEx (Class I, Zone 2, Group IIC, T3 Hazardous Location)\u003c\/li\u003e\n\u003c\/ul\u003e                                         \u003cbr\u003e                                         \u003ch3\u003e\u003cb\u003eDocumentation and Resources\u003c\/b\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/engprd01.hammondpowersolutions.com\/info\/en\/pn\/TX2A0015KHKF\" target=\"_blank\"\u003eEngineering Drawing (PDF) \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/documents.hammondpowersolutions.com\/documents\/Literature\/Low_Voltage_Distribution_(Encapsulated_and_Ventilated)_Brochures\/HPS-Titan-Series-Encapsulated-Transformer-for-Harsh-Environments-Brochure.pdf\" target=\"_blank\"\u003eBrochure \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/www.youtube.com\/@HammondPowerSolutionsIncHPS\/videos\" target=\"_blank\"\u003eHammond Product Application Videos \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/americas.hammondpowersolutions.com\/resources\/\" target=\"_blank\"\u003eFrequently Asked Questions \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"http:\/\/www.hammondpowersolutions.com\/en\/Resources\/categories\/troubleshooting\/\" target=\"_blank\"\u003eTroubleshooting Guide \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/engprd01.hammondpowersolutions.com\/encl\/pn\/DQT4-N4\/pdf\" target=\"_blank\"\u003eEnclosure CAD Drawing (PDF) \u003c\/a\u003e\u003c\/li\u003e\n\u003c\/ul\u003e ","brand":"Hammond Power Solutions","offers":[{"title":"New","offer_id":62209328480415,"sku":"TX2A0015KHKF-New","price":4708.18,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0500\/2349\/7887\/files\/hammond-power-solutions-transformer-new-hammond-power-solutions-tx2a0015khkf-3-phase-transformer-15kva-480d-400y-231v-53687944020127.jpg?v=1766010937","url":"https:\/\/essentialparts.com\/products\/tx2a0015khkf","provider":"Essential Electric Supply","version":"1.0","type":"link"}