{"product_id":"sk3a0075kb3s","title":"SK3A0075KB3S - Hammond Power Solutions 3-Phase 75 kVA 480D-208Y\/120V Aluminum Transformer 60Hz 150C 3R","description":" \t\t\t\t\t\t\t\t\t\t\u003ch2\u003eSK3A0075KB3S\u003c\/h2\u003e                                         \u003cbr\u003e \t\t\t\t\t\t\t\t\t\t\u003cb\u003eSK3A0075KB3S\u003c\/b\u003e is a 3-phase, 75 kVA distribution transformer from Hammond Power Solutions designed for reliable power distribution in commercial and industrial applications.\u003cp\u003eThis transformer features a 480 delta primary voltage and a 208Y\/120 volt secondary voltage configuration, constructed with aluminum windings. It operates at 60 Hz frequency and is rated for 150 degrees Celsius temperature rise. The enclosure is Type 3R, providing protection suitable for outdoor use against rain and snow. It is part of the Sentinel K Series, model D16 SNTL-K K13, optimized for energy efficiency and harmonic handling in non-linear load environments.\u003c\/p\u003e\u003cul\u003e\n\u003cli\u003ePower Rating: 75 kVA\u003c\/li\u003e\n\u003cli\u003ePhase: 3-Phase\u003c\/li\u003e\n\u003cli\u003ePrimary Voltage: 480V Delta\u003c\/li\u003e\n\u003cli\u003eSecondary Voltage: 208Y\/120V\u003c\/li\u003e\n\u003cli\u003eFrequency: 60 Hz\u003c\/li\u003e\n\u003cli\u003eWinding Material: Aluminum\u003c\/li\u003e\n\u003cli\u003eTemperature Rise: 150°C\u003c\/li\u003e\n\u003cli\u003eEnclosure Type: 3R (Rainproof)\u003c\/li\u003e\n\u003cli\u003eSeries: Sentinel K (SNTL-K)\u003c\/li\u003e\n\u003cli\u003eMounting Type: Floor (typical for DH3 case style)\u003c\/li\u003e\n\u003c\/ul\u003e\u003cp\u003eAt \u003cb\u003eEssential Parts\u003c\/b\u003e, we offer \u003cb\u003efast shipping\u003c\/b\u003e, \u003cb\u003elowest price\u003c\/b\u003e, and \u003cb\u003eexpert support\u003c\/b\u003e to help you get the right product every time.\u003c\/p\u003e \t\t\t\t\t\t\t\t\t\t\u003cbr\u003e                                          \t\t\t\t\t\t\t\t\t\t\u003ch3\u003e\u003cb\u003eSpecifications\u003c\/b\u003e\u003c\/h3\u003e \t\t\t\t\t\t\t\t\t\t\u003cul\u003e \t\t\t\t\t\t\t\t\t\t\t\u003cli\u003ePart Number: SK3A0075KB3S\u003c\/li\u003e                                             \u003cli\u003eManufacturer : Hammond Power Solutions\u003c\/li\u003e\n\u003cli\u003eBrand : Hammond Power Solutions\u003c\/li\u003e\n\u003cli\u003eCategory : Transformer\u003c\/li\u003e\n\u003cli\u003ePhase : 3\u003c\/li\u003e\n\u003cli\u003eEnclosure Grade : Standard\u003c\/li\u003e\n\u003cli\u003eDuty : General Duty\u003c\/li\u003e\n\u003cli\u003eFrequency : 60Hz\u003c\/li\u003e\n\u003cli\u003ePrimary Voltage : 480D\u003c\/li\u003e\n\u003cli\u003ePrimary Connection : Delta\u003c\/li\u003e\n\u003cli\u003ePrimary FCAN (NPL) : 2x2.5%\u003c\/li\u003e\n\u003cli\u003ePrimary FCBN (NPL) : 4x2.5%\u003c\/li\u003e\n\u003cli\u003eSecondary Voltage : 208Y\/120\u003c\/li\u003e\n\u003cli\u003eSecondary Connection : Wye-N\u003c\/li\u003e\n\u003cli\u003eMaterial : Aluminum\u003c\/li\u003e\n\u003cli\u003eTemperature Rise : 150Â°C\u003c\/li\u003e\n\u003cli\u003eInsulation Class : 220Â°C\u003c\/li\u003e\n\u003cli\u003eEKVA : 88.4237\u003c\/li\u003e\n\u003cli\u003eEfficiency Regulation : DOE 2016 (US), NRCAN 2019 (Canada), NMX 2021 (Mexico)\u003c\/li\u003e\n\u003cli\u003eSeismic Compliance : IBC 2018 (Sds=2.0, z\/h=1, lp=1.5)\u003c\/li\u003e\n\u003cli\u003eSound Level : 53 dBA (NEMA ST-20)\u003c\/li\u003e\n\u003cli\u003eImpedance (Std) : 2.5% - 6.5%\u003c\/li\u003e\n\u003cli\u003eSecondary Termination (NPL) : Mechanical Lugs\u003c\/li\u003e\n\u003cli\u003eEnclosure Type : Type 3R \/ IP24\u003c\/li\u003e\n\u003cli\u003eEnclosure Finish : ANSI 61 Grey, UL50\u003c\/li\u003e\n\u003cli\u003eEnclosure PN (NPL) : DH3-N3R\u003c\/li\u003e\n\u003cli\u003eEnclosure Dimensions : 36in\/915mm(H), 28.25in\/718mm(W), 27in\/686mm(D)\u003c\/li\u003e\n\u003cli\u003eElectrostatic Shield : Single\u003c\/li\u003e\n\u003cli\u003eNameplate : Standard\u003c\/li\u003e\n\u003cli\u003eStandard kVA : 75\u003c\/li\u003e\n\u003cli\u003eVector Configuration : Dyn1 (-30Â°)\u003c\/li\u003e\n\u003cli\u003eSeismic Standard Value : IBC 2018\u003c\/li\u003e\n\u003cli\u003eOSHPD : No\u003c\/li\u003e\n\u003cli\u003eSeismic IP : lp=1.5\u003c\/li\u003e\n\u003cli\u003eSeismic ZH : z\/h=1\u003c\/li\u003e\n\u003cli\u003eSeismic SDS Value : Sds=2.0\u003c\/li\u003e\n\u003cli\u003eEnclosure IR Window : No\u003c\/li\u003e \t\t\t\t\t\t\t\t\t\t\u003c\/ul\u003e                                         \u003cbr\u003e                                         \u003ch3\u003e\u003cb\u003eProduct Data\u003c\/b\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003eUPC : 803423126629\u003c\/li\u003e\n\u003cli\u003eWeight : 575 \u003c\/li\u003e\n\u003cli\u003eCertification : CSA, UL\u003c\/li\u003e\n\u003c\/ul\u003e                                         \u003cbr\u003e                                         \u003ch3\u003e\u003cb\u003eDocumentation and Resources\u003c\/b\u003e\u003c\/h3\u003e\u003cul\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/engprd01.hammondpowersolutions.com\/info\/en\/pn\/SK3A0075KB3S\" target=\"_blank\"\u003eEngineering Drawing (PDF) \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/documents.hammondpowersolutions.com\/documents\/Literature\/Low_Voltage_Distribution_(Encapsulated_and_Ventilated)_Brochures\/HPS-Sentinel-Energy-Efficient-Low-Voltage-Distribution-Selection-Guide.pdf\" target=\"_blank\"\u003eBrochure \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/www.youtube.com\/@HammondPowerSolutionsIncHPS\/videos\" target=\"_blank\"\u003eHammond Product Application Videos \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/americas.hammondpowersolutions.com\/resources\/\" target=\"_blank\"\u003eFrequently Asked Questions \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"http:\/\/www.hammondpowersolutions.com\/en\/Resources\/categories\/troubleshooting\/\" target=\"_blank\"\u003eTroubleshooting Guide \u003c\/a\u003e\u003c\/li\u003e\n\u003cli\u003e\u003ca href=\"https:\/\/engprd01.hammondpowersolutions.com\/encl\/pn\/DH3-N3R\/pdf\" target=\"_blank\"\u003eEnclosure CAD Drawing (PDF) \u003c\/a\u003e\u003c\/li\u003e\n\u003c\/ul\u003e ","brand":"Hammond Power Solutions","offers":[{"title":"New","offer_id":62208959283359,"sku":"SK3A0075KB3S-New","price":5965.02,"currency_code":"USD","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/0500\/2349\/7887\/files\/hammond-power-solutions-transformer-new-sk3a0075kb3s-hammond-power-solutions-3-phase-75-kva-480d-208y-120v-aluminum-transformer-60hz-150c-3r-53687915675807.jpg?v=1766010926","url":"https:\/\/essentialparts.com\/products\/sk3a0075kb3s","provider":"Essential Electric Supply","version":"1.0","type":"link"}